Pilot's Commercial and Industrial (C&I) Battery Energy Storage System (BESS) PL-ESS-500/1075-0.4-L(DCplusAC)
- Save construction cost:In remote areas, off-grid energy supply systems are often more cost-effective than connecting to the grid.
- Ensure reliable power supply:The "wind + solar + diesel" hybrid architecture, combined with energy storage system, ensures power supply continuity and improves power quality.
- On-site consumption of wind and solar energy:Utilize the energy storage system to fully absorb wind and solar resources, maximizing energy savings and emission reductions.
- Flexible deployment and expansion:Highly integrated cabinet design allows for quick deployment, reduces on-site debugging and installation workload, and allows for flexible expansion.
- Applications:Best choose for Oilfield, Mines, Island, Remote Communities, and so on.
Wind-Solar-Diesel-BESS All-in-One Cabinet
- Grid-Connected Operation:Demand response, peak shaving, dynamic capacity expansion, demand management, anti-backflow.
- Off-Grid Operation:Islanding detection, on/off-grid switching, frequency and voltage emergency response, black start.
- Microgrid EMS:Load Forecasting, Generation Forecasting,Economic optimization,Carbon emission management,AGC/AVC,Demand response,Islanding detection,Black-start.
- Industrial Applications Sectors:Commercial building, Healthcare, Manufacturing, Data center, and so on.
Hierarchical Microgrid Control System
- PV: Select PV parking shed, rooftop PV and BIPV according to the location.
- BESS:Choose different capacity according to the site needs.
- Charging Station:Configure charging piles with different powers and types according to the charging requirements.
Solar-BESS-Charging System
Specification
Model | PL-ESS-500/1075-0.4-L(DCplusAC) |
DC-side parameters | |
Cell type | LFP energy storage cell |
Grouping method | 1P238S*6 |
Nominal energy | 1280kWh |
Working voltage | 666V~856V |
Rated charge/discharge rate | 0.5P |
AC-side parameters | |
AC rated power | 500kW |
Rated power grid voltage | 380V |
Rated power grid frequency | 50HZ |
System parameters | |
System efficiency | ≥90% |
Depth of discharge | 95% DoD |
Number of cycles | ≥8000 |
IP rating | IP54(PACKIP67) |
Operating temperature | -30℃~55℃ |
Cooling mode | Optional air cooling / liquid cooling |
Fire protection system | Perfluorohexanone PACK-level fire protection + active early warning |
Dimensions | DC side: 6058*1300*2000 (mm) AC side: 1300*1300*2200 (mm) |
Weight | 18t |
Containerized BESS (Air Cooling)
Type | Energy (MWh) | Power (MW) | DC Voltage | Grouping | Num. of Packs | Num. of Clusters | L*W*H (mm) | Weight (Ton) | Cell (Ah) | |
1 | 15-foot Container, 1000V system | 0.52 | 0.25 | 627 | 1P14S | 14 | 3 | 4515*2438*2896 | 12 | 280 |
2 | 20-foot Container, 1000V system | 1.28 | 0.64 | 761.6 | 1P14S | 14 | 6 | 6138*2438*2896 | 18 | 280 |
3 | 40-foot Container, 1000V system | 2.56 | 1.28 | 761.6 | 1P14S | 17 | 12 | 12192*2438*2896 | 35 | 280 |
4 | 40-foot Container, 1500V system | 3.27 | 1.64 | 1299.2 | 1P14S | 29 | 9 | 12192*2438*3200 | 46 | 280 |
Containerized BESS (Liquid Cooling)
Type | Energy (MWh) | Power (MW) | DC Voltage | Grouping | Num. of Packs | Num. of Clusters | L*W*H (mm) | Weight (Ton) | Cell (Ah) | |
1 | 20-foot Container, 1500V system | 2.75 | 1.5 | 1228 | 1P14S | 8 | 8 | 6058*2438*2591 | 28 | 280 |
2 | 20-foot Container, 1500V system | 1.28 | 0.64 | 761.6 | 1P14S | 17 | 6 | 6638*2438*2896 | 18 | 280 |
3 | 20-foot Container, 1500V system | 2.56 | 1.28 | 761.6 | 1P14S | 17 | 12 | 6138*2438*2896 | 35 | 280 |
4 | 20-foot Container, 1500V system | 3.27 | 1.64 | 1299.2 | 1P14S | 29 | 9 | 6638*2438*2896 | 46 | 280 |